FO Universal wbGGFR Safety / U-DQ(ZN)BH

Safety cable E30*, up to 60 fibres G.652.D

metal-free, water resistant, rodent protection,
in accordance with IEC 60332-1-2 and IEC 60332-3-24
30 minutes System Circuit Integrity* with reference to DIN 4102-12

1 ≤ 12 fibres
2 Flame retardant protective coating
3 Glass armour
4 Ripcord
5 FR/LS0H sheath

Description

Metal-free fibre optic safety cable with multiple loose tubes, up to 60 fibres.
The optimal combination of flame retardant fibre coating and flame-inhibiting stabilizing elements ensures enhanced functional integrity (System Circuit Integrity*) in case of fire for 30 minutes (transmission of audio, video and 1Gbit/s signals approved by a certified test report).

Safety applications in tunnels, underground railways, banks, insurance companies, large-scale industry.
LAN backbone.
Indoor and outdoor cabling.
Can be installed in cable platforms, trays, ducts and vertical shafts.
Can be spliced in FO distributors.

Optical fibre E9/125 G.652.D: see fibre data sheet.
These cables are available with different types of optical fibre.

Temperature rangestorage: -25 / +70°CIEC 60794-1-22 F1
 during installation: -10 / +50°C 
 in operation: -25 / +60°C 
Tensile performance:IEC 60794-1-21 E1  
Crush resistance:IEC 60794-1-21 E3  
Repeated bending:IEC 60794-1-21 E6  
Torsion:IEC 60794-1-21 E7  
Bend:IEC 60794-1-21 E11  
Water penetration:IEC 60794-1-22 F5  

* System Circuit Integrity is dependent on installation method.

Imprint

DATWYLER «cable type» «Datwyler designation» «DIN designation» «no. of fibres» «fibre type» «add. text» «batch no.» «meter marks»

Zero halogen, no corrosive gases

IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2

Flame propagation

IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2

Flame spread

IEC 60332-3-24, EN 50266-2-4, VDE 0482-266-2-4

Smoke density

IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2

Circuit Integrity

IEC 60331-11, IEC 60331-25 (FE90), EN 50200 PH90, VDE 0482-200

System circuit integrity

according to DIN 4102 part 12, VKF Fire Safety Application No. 24176

Reaction to fire (Euroclasses)

not classified

Documentation

ENDENLFRCNES
Product Datasheet
Tender text

Versions

Article No.ProductNumber of fibresFibre typeLoose TubesSheath colourSheath Ø [mm]Weight [kg/km]Bending radius [mm]Tensile load [N]Crush resistance continuous [N]Crush resistance short term [N]Fire load [kWh/km]Fire load [MJ/km]
194430wbGGFR Safety 1 x 1212E9/125 G.652.D OS21red12,51661906000300050007332639
190223wbGGFR Safety 2 x 1224E9/125 G.652.D OS22red12.51661906000300050007332639
190224wbGGFR Safety 3 x 1236E9/125 G.652.D OS23red12.51661906000300050007332639
190225wbGGFR Safety 4 x 1248E9/125 G.652.D OS24red12.51661906000300050007332639
190226wbGGFR Safety 5 x 1260E9/125 G.652.D OS25red12.51661906000300050007332639

Similar Products

FO Universal ZGGFR / U-DQ(ZN)BH

up to 24 fibres G.652.D, Euroclass Dca

FO Universal ZGGFR / U-DQ(ZN)BH - yellow

up to 24 fibres G.652.D, Euroclass Dca

FO Universal ZGGFR / U-DQ(ZN)BH_

up to 24 fibres G.652.D (BLO), Euroclass Dca