JE-H(St)HRH...Bd FE180 E30-E90 fire alarm

Fire alarm cable with steel wire braiding, max. 225V, Keram

halogen-free, with improved fire characteristics,
with reference to VDE 0815,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331, EN 50200,
System Circuit Integrity E30-E90* in accordance with DIN 4102-12 

Conductor: solid
Insulation: cross-linked polymer, halogen-free
3 Drain wire: tinned copper, Ø 0.8 mm 
Inner covering: plastic tape, halogen-free 
Shielding: Al-laminated plastic foil, halogen-free 
Inner sheath: FRNC/LS0H
Armouring: galvanised steel wire band
8 Sheath: FRNC/LS0H

Description

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The steel wire braiding serves as mechanical protection. The fire alarm cables correspond to the demands of System Circuit Integrity E30-E90* in accordance  with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 110V.
Permitted operating temperature at conductor of +70°C.

ConductorBare copper, solid, 0.8 mm diameter, VDE 0815
InsulationFire-resistant, cross-linked, high-performance Keram special compound, EN 50290-2-26
Core coloursAccording to VDE 0815, bundles identified by numbered tape
SeparatorPEPT “Plastic Tape”
ShieldingAl-laminated tape with tinned copper drain wire Ø 0.8 mm
Inner sheathFlame retardant polyolefin compound, VDE 0819 part 107, EN 50290-2-27 and VDE 0250-214 “HM2“
ArmouringGalvanised steel wire braid
Outer sheathFlame retardant polyolefin compound, VDE 0819 part 107, EN 50290-2-27 and VDE 0250-214 “HM 2“
Sheath colourRed
Insulation resistanceminimum 100 MΩ x km
Loop resistancemaximum 73.2 Ω/km at 0.8 mm
Capacitance unbalancemaximum 120 nF/km at 800 Hz
Capacitance couplingK maximum 200 pF/100m at 800 Hz
Rated voltagemaximum 225 V
Test voltage500 V, 50 Hz Core/Core
 2000 V, 50Hz, Core/Screen
Minimum bending radius7.5 x D (D = outer diameter)
Crush resistance≥ 1000 N/10 cm
Impact≥ 10 impacts
Operating temperaturepermanent installation-30°C to +70°C
 during installation-5°C to +50°C
System Circuit Integrity dependent on installation method.

Zero alogeni, no gas corrosivi

IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA

Propagazione delle fiamme

IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1

Diffusione delle fiamme

IEC 60332-3-22/-24 Cat. A/C, EN 60332-3-22/-24 Cat. A/C, VDE 0482-332-3-22/-24 Cat. A/C, AREI-RGIE Art.104-F2

Integrità del circuito (FE180)

IEC 60331-11/-21 (180 minutes), VDE 0472 part 814 (FE180), IEC 60331-1, IEC 60331-2 (120 minutes ), EN 50200, VDE 0482-200 (PH120) and EN 50362, VDE 0482-362 (120 minutes), BS 6387 C/W/Z, AREI-RGIE Art.104-FR1

Integrità del circuito di sistema

DIN 4102 part 12, AREI-RGIE Art.104-FR2

Documentation

ENDENLFRCNESIT
Product Datasheet
Tender text
MPA Certificate

Versions

Article No.ProdottoNumero di coppieNumero di coreDiametro [mm]Colore della guainaGuaina Ø [mm]Peso [kg/km]Tasso di Cu [kg/km]Carico di fuoco [kWh/m]PU
188119JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 2x2x0.8 mm220.8 mmrosso9.2124.6250.26al metro
188120JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 4x2x0.8 mm420.8 mmrosso12193.7450.39al metro
188127JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 8x2x0.8 mm820.8 mmrosso18.2423.7850.93al metro
188128JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 12x2x0.8 mm1220.8 mmrosso19.1487.91261.01al metro
188129JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 20x2x0.8 mm2020.8 mmrosso22.5679.12061.32al metro
188346JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 32x2x0.8 mm3220.8 mmrosso26.7910.83261.72al metro
Additional dimensions available on request.