CU 7702 4P FRNC/GG/FRNC

Data cable, S/FTP, Category 7A, AWG22, Euroclass Cca

with rodent protection and UV resistant cable sheeth

1 Inner conductor: AWG22 Bare copper wire
2 PE insulated conductor: 1.5 mm Ø
3 Screen (pair): Alu PETP foil
4 Overall screen: Tinned braided copper
5 Sheath: FRNC/LSZH orange RAL 2003
6 Rodent protection: with glass rovings
7 Ripcord
8 Outer sheath: FRNC/LSZH black

Description

Applicable for outdoor installation due to rodent protection and UV resistant outer cable sheath.
Robust cable design with a high mechanical stability.
Electrically and mechanically superior quality Cat.7A data cable - exceeds the requirements of ISO/IEC 11801-1, IEC 61156-5, EN 50173-1 and EN 50288-9-1.
Excellent shielding effect due to individually screened pairs and overall copper braid.
Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801-1.
Data cable for structured premise cabling with enhanced mechanical and fire protection performance.
Designed for installation in Tunnels, Metro-Systems and Buildings with augmented requirements.
With rodent protection and UV protected outer sheath. Installation in ducts, tubes and on cable support systems.
Suitable for all ICT network applications up to class FA applications (1000 MHz) in accordance with EN 50173-1 and ISO/IEC 11801.
Supports 10Base-T, 100Base-T, 1GBase-T (1000Base-T) and 10GBase-T.
Applicable for Power over Ethernet PoE / PoE+ / 4PPoE.
Category   5e66A7CATV7A 
Frequency [MHz]141010025050060086210001200
Attenuation [dB/100m]1.73.45.316.9274042535662
NEXT [dB]1031031031031039896929085
PS NEXT [dB]1001001001001009593898782
ACR-N [dB]1011009886765854393423
PS-ACR-N [dB]98979583735551363120
ACR-F [dB]10910710593837065575446
PS-ACR-F [dB]10610410290806762545143
Return loss [dB]26303333282625242321
These performance data are typical measured values.
Category:Cat.7A
Attenuazione di accoppiamento:85 dB
Ritardo Skew:15 ns/100 m
Impedenza a 100 MHz, ±5Ω:100 Ω
Loop resistance at 20°C:< 116 Ω/km
Near end unbalance attenuation LCL at 1-600 MHz:40 dB
NVP %:76
operating capacity:43 pF/m
Transfer impedance 1/10/30 MHz:< 5/5/8 mΩ/m
10Base-T, 100Base-T, 1000Base-T, 2.5GBase-T, 5GBase-T, 10GBase-T
Curvatura minima durante l'installazione:96 mm
Minimum bending radius permanently installed:48 mm
Resistenza alla trazione (4P):150 N
Resistenza minima allo schiacciamento / 10cm:1,000 N
Minimum number of impacts:10
Installation temperature:0 °C - +50 °C
Operating temperature:-20 °C - +60 °C

Reaction to fire (Euroclasses)

EN 13501-6: Cca

Colore del cavo

white-blue/bluewhite-orange/orangewhite-green/greenwhite-brown/brown(with longitudinal stripes)in accordance with IEC 60189 and IEC 60708

Impronta

DATWYLER «cable type» «additional text» «batch number» «meter marks»

Zero alogeni, no gas corrosivi

IEC 60754-1/-2, EN 60754-1/-2

Propagazione delle fiamme

IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2

Densità del fumo

IEC 61034-1/-2, EN 61034-1/-2

PoE

IEEE 802.3at

EMC

shielded

Classe di segregazione

d

Cat./Class

Cat 7A / Class FA - limit values as specified by IEC 61156-5 and EN 50288-9-1 guaranteed

Documentation

ENDENLFRCNESIT
Product Datasheet
GHMT PVP Certificates

Versions

Article No.DoPProdottoReaction to fire (Euroclasses)Dimensioni n x p x [mm (AWG)]GuainaColore della guainaGuaina Ø [mm]Peso [kg/km]Tasso di Cu [kg/km]Carico di fuoco [MJ/m]Carico di fuoco [kWh/m]PU
19435400CZCU 7702 4PCca-s1a,d1,a14 x 2 x 0.62 (AWG22)FRNC/LS0Hnera12.016734.91.98 MJ/m0.55al metro

Prodotti correlati

CU 8203 4P

Data cable, S/FTP, Category 8.2, AWG23, Euroclass Dca

CU 8203 4P

Data cable, S/FTP, Category 8.2, AWG23, Euroclass Cca

CU 8203 4P

Data cable, S/FTP, Category 8.2, AWG23, Euroclass B2ca