FE180 E30 CL

Safety cable, 0.6/1kV, armoured with rodent protection, Keram

halogen-free, with improved fire characteristics,
with reference to SEV TP 20B/3C and CENELEC HD 604 S1 part 5.H 

Conductor: solid / stranded
2  Fire barrier: high-peformance Keram compound
Insulation: cross-linked polymer, zero halogen
Filler: flame retardant, zero halogen
Inner Sheath: Polyolefin flame retardant, low smoke, zero halogen
Armouring: galvanised steel tape
Sheath: FRNC/LSZH

Descripción

Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.

Conductor:
 
Bare copper, solid or stranded, IEC 60228 and EN 60228
(≥16 mm2: VDE 0295)
Conductor insulation:
 

Special compound, HD 604 S1 part 5 H
(≥16 mm2: double-layer insulation, special compound, VDE 0266 "HXI1")

Filler:
 

HD 604 S1 part 5 H
(≥16 mm2: halogen-free polyolefin compound)

Inner sheath:
 

Compound, HD 604 S1 part 5 H
(≥16 mm2: Polyolefin compound, VDE 0276-604, CENELEC HD 604 S1 "HM 4", flame-retardant)

Armouring (rodent  protection):Single-core cable with copper tape (CLCU), multicore cable with galvanised steel tape (CL)
Outer Sheath:
 

Compound, HD 604 S1 part 5 H
(≥16 mm2: in accordance with CENELEC HD 308 S2 and VDE 0293)

Core Colours:

CENELEC HD 308 S2

Sheath colour:orange 

 

Nominal voltage:

0.6/1kV 

Test voltage:3500V, 50Hz

Minimum bending radius

during and permanent installation:

15 x D (single core cable) 

12 x D (multicore cable)

(D = outer diameter)

Operating temperature

permanent installation:

-45°C to +90°C

 

during installation:

-5°C to +50°C

* System Circuit Integrity is dependent on installation method

Cero halógenos, gases no corrosivos

IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, SEV TPV11, AREI-RGIE Art.104-SA

Propagación de la flama

IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, SEV TP 20B/3C 3.4.1.1, AREI-RGIE Art.104-F1

Dispersión de la flama

IEC 60332-3-24 Cat. C, EN 60332-3-24 Cat. C, VDE 0482-332-3-24 Cat. C, SEV TP 20B/3C 3.4.1.3, AREI-RGIE Art.104-F2

Integridad de circuito (FE180)

IEC 60331-11/-21 (180 minutes), VDE 0472 part 814 (FE180), IEC 60331-1, IEC 60331-2 (120 minutes ), EN 50200, VDE 0482-200 (PH120) and EN 50362, VDE 0482-362 (120 minutes), BS 6387 C/W/Z, AREI-RGIE Art.104-FR1

Integridad del Sistema de Circuito

FE180 E30 CL: according to DIN 4102-12, VKF Fire Safety Application No. 24176, AREI-RGIE Art.104-FR2

Documentos

ENDENLFRCNESIT
Ficha técnica del producto

Versiones

N° de artículoProductoNúmero de núcleosDiámetro [mm2]Forro Ø [mm]Peso [kg/km]Prop. Cu [kg/km]Carga de fuego [kWh/m]Conductor
193886FE180 E30 CL31.511211.4430.46de corrido
187199FE180 E30 CL32.512255.7720.50de corrido
191097FE180 E30 CL3414372.81150.69de corrido
191121FE180 E30 CL3615.84871730.90de corrido
188354FE180 E30 CL31018655.22881.20de corrido
191595FE180 E30 CL42.514298.2960.56de corrido
187167FE180 E30 CL44164081540.79de corrido
188352FE180 E30 CL4617538.92301.06de corrido
191038FE180 E30 CL52.514396.71200.76de corrido
188350FE180 E30 CL5416488.21921.05de corrido
188353FE180 E30 CL5617.5642.92881.28de corrido
188397FE180 E30 CL51021970.84801.76de corrido
187197FE180 E30 CL72.516481.21680.91de corrido
188355FE180 E30 CL7619800.74031.53de corrido
188356FE180 E30 CL710231211.96722.13de corrido
192461FE180 E30 CL81.515404.21150.85de corrido
187128FE180 E30 CL82.516504.21921.04de corrido
191104FE180 E30 CL8418683.63081.36de corrido
Additional dimensions available on request