N2XH

Safety cable, single-core, 0.6/1kV, Euroclass Cca

Halogen-free, with improved fire characteristics,
CENELEC HD 604 S1, VDE 0276-604

1 Conductor: solid/stranded 
2 Insulation: zero halogen
3 Sheath: FRNC/LSZH

Descripción

For permanent installation in dry, damp or wet areas, on or behind plasterwork or in walls or concrete. Also suitable for outdoor applications. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.
Conductor:Bare copper, solid or stranded, IEC 60228, EN 60228 (VDE 0295)
Insulation:Cross-linked Polyethylene, CENELEC HD 604 S1 and VDE 0276-604
Filler:Halogen-free compound or plastic tape
Outer sheath:Polyolefin compound, CENELEC HD 604 S1, VDE 0276-604 “HM4”
Core colours:CENELEC HD 308 S2 and VDE 0293
Sheath colour:Black
Imprint:On request
Nominal voltage:0.6/1kV     
Test voltage:4000V, 50Hz 
Minimum bending radiusduring and permanent installation:15* x D (single-core cable)
  (D = outer diameter)
 permanent installation:*50% reduction if installation
  at 30°C and with a template
Operating temperaturepermanent installation:-45°C to +90°C
 during installation:-5°C to +50°C
Additional dimensions available on request.

Reacción al fuego (Euroclase)

EN 13501-6: Cca

Cero halógenos, gases no corrosivos

IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA

Propagación de la flama

IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1

Dispersión de la flama

IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Art.104-F2

Densidad de humo

IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD

Documentos

ENDENLFRCNESIT
Ficha técnica del producto

Versiones

N° de artículoProductoReacción al fuego (Euroclasses)Número de núcleosSección transversal [mm²]Forro Ø [mm]Peso [kg/km]Prop. Cu [kg/km]Carga de fuego [kWh/m]ConstrucciónConductorUE
17000301CZN2XH-O 1 x 16Cca-s1a,d2,a11169.82301540.36Ltrenzadopor metro
17000401CZN2XH-O 1 x 25Cca-s1a,d2,a112511.73452400.48Lstrandedpor metro
17000501CZN2XH-J 1 x 25Cca-s1a,d2,a112511.73452400.48PEstrandedpor metro
17001001CZN2XH-O 1 x 35Cca-s1a,d2,a113512.94453360.55Lstrandedpor metro
17002601CZN2XH-J 1 x 35Cca-s1a,d2,a113512.94453360.55PEtrenzadopor metro
17000601CZN2XH-O 1 x 50Cca-s1a,d2,a115014.46004800.65Lstrandedpor metro
17000701CZN2XH-J 1 x 50Cca-s1a,d2,a115014.46004800.65PEstrandedpor metro
17001801CZN2XH-O 1 x 70Cca-s1a,d2,a117016.28106720.84Lstrandedpor metro
17003001CZN2XH-J 1 x 70Cca-s1a,d2,a117016.28106720.84PEtrenzadopor metro
17000801CZN2XH-O 1 x 95Cca-s1a,d2,a119518.19869120.97Lstrandedpor metro
17000901CZN2XH-J 1 x 95Cca-s1a,d2,a119518.110709120.97PEtrenzadopor metro
17001901CZN2XH-O 1 x 120Cca-s1a,d2,a1112019.6133011521.10Ltrenzadopor metro
17002501CZN2XH-J 1 x 120Cca-s1a,d2,a1112019.6133011521.10PEstrandedpor metro
17002001CZN2XH-O 1 x 150Cca-s1a,d2,a1115021.5162014401.43Lstrandedpor metro
19156601CZN2XH-J 1 x 150Cca-s1a,d2,a1115021.5162014401.43PEstrandedpor metro
17001101CZN2XH-O 1 x 185Cca-s1a,d2,a1118522.8199017761.72Lstrandedpor metro
17003101CZN2XH-J 1 x 185Cca-s1a,d2,a1118524.7199017761.72PEtrenzadopor metro
17001201CZN2XH-O 1 x 240Cca-s1a,d2,a1124026.4257023042.02Lstrandedpor metro
17001301CZN2XH-O 1 x 300Cca-s1a,d2,a1130029.8318028802.58Ltrenzadopor metro
17002901CZN2XH-J 1 x 300Cca-s1a,d2,a1130029.8318028802.58PEstrandedpor metro