N2XCH

Safety cable, 0.6/1kV, Euroclass Cca

halogen-free, with improved fire characteristics,
CENELEC HD 604 S1, VDE 0276-604 

1 Conductor: solid/ stranded
2 Insulation: cross-linked PE, zero halogen
3 Filler: flame retardant, zero halogen
4 Concentric conductor: bare copper wire
5 Reinforcing helix: bare copper tape
6 Separator: plastic tape
7 Sheath: FRNC/LSZH

Descripción

For permanent installation in dry, damp or wet areas, on or behind plasterwork or in walls or concrete. Also suitable for outdoor applications.
The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.

Conductor:Bare copper, solid or stranded, IEC 60228, EN 60228, (VDE 0295)
Insulation:Cross-linked Polyethylene, CENELEC HD 604 S1, VDE 0276-604
Filler:Halogen-free compound or plastic tape
Concentric conductor:Bare copper wires with reinforced helix
Separator:Plastic tape
Outer sheath:Polyolefin compound, CENELEC HD 604 S1 and VDE 0276-604 “HM4”
Core colours:CENELEC HD 308 S2 and VDE 0293
Sheath colour:Black
Imprint:On request
Nominal voltage:0.6/1kV 
Test voltage:4000V, 50Hz 
Minimum bending radiusduring and permanent installation:12 x D (multicore cable)
  (D = outer diameter)
Operating temperaturepermanent installation:-45°C to +90°C
 during installation:-5°C to +50°C
Additional dimensions available on request.

Reacción al fuego (Euroclasses)

EN 13501-6:Cca-s1,d1,a1

Cero halógenos, gases no corrosivos

IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA

Propagación de la flama

IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1

Dispersión de la flama

IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Art.104-F2

Densidad de humo

IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD

Documentos

ENDENLFRCNESIT
Ficha técnica del producto

Versiones

N° de artículoDoPProductoNumber of CoresDiameter [mm²]Forro Ø [mm]Peso [kg/km]Prop. Cu [kg/km]Carga de fuego [kWh/m]ConstrucciónConductor
17017204CZN2XCH 3 x 50/25350/2529.0199117232.723Lsolid
17017504CZN2XCH 3 x 70/35370/3534.8283124104.113Lstranded
17019704CZN2XCH 3 x 95/50395/5037.7435132964.603Lstranded
17017404CZN2XCH 3 x 120/703120/7041.6527142365.553Lstranded
17019804CZN2XCH 3 x 150/703150/7045.6545151006.683Lstranded
17018404CZN2XCH 4 x 50/25450/2534.4260022033.383LNstranded
17018504CZN2XCH 4 x 70/35470/3540.5355030824.483LNstranded
17018604CZN2XCH 4 x 95/50495/5044.4480042085.443LNstranded
17018704CZN2XCH 4 x 120/704120/7048.3650053826.383LNstranded
17018804CZN2XCH 4 x 150/704150/7053.2795065407.973LNstranded
17018904CZN2XCH 4 x 185/954185/9558.9997081599.863LNstranded

Related products

NHXMH

Power cable, 300/500V

FO Indoor szGGFR / J-B(ZN)BH

Shielded power cable, 300/500V

N2XH

Safety cable, single-core, 0.6/1kV, Euroclass Cca