J-H(St)H...Bd fire alarm .

Fire alarm cable, max. 300V

halogen-free, with improved fire characteristics,
VDE 0815 

1 Conductor: solid
2 Insulatio: halogen-free polymer compound
3 Separator: plastic tape
4 Drain wire: tinned copper
5 Shielding: Al-laminated plastic foil
6 Sheath: FRNC/LSZH

Descripción

Installation cable with electrostatic shield for areas vulnerable to fire and with high concentration of people and property value. For ICT systems for lossless data and signal transmission. Suitable for laying in dry and humid rooms, on-wall and in-wall, also for outdoor use.
No underground laying. Not to be used for high-voltage transmission.
Permitted operating temperature at conductor of +70°C.

ConductorBare copper, solid, 0.6 or 0.8 mm diameter
InsulationHalogen-free polymer compound, EN 50290-2-26
Core idendificationDIN VDE 0815 (different colours)
StrandingCores twisted to star-quads and quads to units
ShieldingAl-laminated plastic foil with drain wire, copper tinned
Outer sheathHalogen-free polymer compound, EN 50290-2-27
Sheath colourRed
Rated voltagemax. 300V
Test voltage800V 50Hz
Conductor resistance Loop

0,6mm max. 130 Ω / km;

 

0,8mm max. 73,2 Ω / km

Insulation resistance

min. 100 MΩ x km

Capacitymax. 120 nF/km
Minimum bending radiuspermanent installation2.5 x D
 during installation7.5 x D (D = outer diameter)
Operating temperaturepermanent installation-30 °C bis +70 °C
 during installation- 5 °C bis +50 °C

Additional dimensions available on request. 

Cero halógenos, gases no corrosivos

IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA

Propagación de la flama

IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1

Dispersión de la flama

IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Art.104-F2

Densidad de humo

IEC 61034-1/-2, EN 61034-1/-2 , VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD

Documentos

ENDENLFRCNESIT
Ficha técnica del producto
Texto para licitaciones

Versiones

N° de artículoProductoNumber of PairsNumber of CoresDiameter [mm]Forro Ø [mm]Peso [kg/km]Prop. Cu [kg/km]Carga de fuego [kWh/m]Dimensiones n x p x [mm]
184707J-H(St)H...Bd120.86.056150.121 x 2 x 0.8
157892J-H(St)H...Bd220.87.069250.162 x 2 x 0.8
157893J-H(St)H...Bd420.811.0136450.294 x 2 x 0.8
157894J-H(St)H...Bd620.811.0152650.356 x 2 x 0.8
157895J-H(St)H...Bd1020.813.02301060.5510 x 2 x 0.8
1172017J-H(St)H...Bd2020.821.05082061.2120 x 2 x 0.8
1172018J-H(St)H...Bd3020.822.05993071.3630 x 2 x 0.8
1172019J-H(St)H...Bd4020.825.07874071.6740 x 2 x 0.8
1172021J-H(St)H...Bd8020.834.014768093.1880 x 2 x 0.8
1172022J-H(St)H...Bd10020.838.0180510104.07100 x 2 x 0.8

Similar Products

NHXMH

Power cable, 300/500V

FO Indoor szGGFR / J-B(ZN)BH

Shielded power cable, 300/500V

N2XH

Safety cable, single-core, 0.6/1kV, Euroclass Cca