FE180 E30

Safety cable, 0.6/1kV, Keram

halogen-free, with improved fire characteristics,
in accordance to SEV TP 20B/3C and CENELEC HD 604 S1 part 5.H
30 minutes system circuit integrity* with reference to DIN 4102-12

1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Sheath: FRNC/LSZH

Description

Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.
Conductor:
 
Bare copper, solid, IEC 60228 and EN 60228
(≥16 mm2: VDE 0295)
Conductor insulation:

Special compound, HD 604 S1 part 5 H

Filler:
 

HD 604 S1 part 5 H

Outer Sheath:
 

Compound, HD 604 S1 part 5 H

Core Colours:

CENELEC HD 308 S2

Sheath colour:orange
Nominal voltage:0.6/1kV
Test voltage:3500V, 50Hz
Minimum bending radiusduring and permanent installation:15* x D (single-core cable)
  12* x D (multicore cable)
  (D = outer diameter)
 permanent installation:*50% reduction if installation at
  30°C and with a template
Operating temperaturepermanent installation:-45°C to +90°C
 during installation:-5°C to +50°C
System Circuit Integrity is depemndent on installation method.

Zero halogen, no corrosive gases

IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, SEV TPV11, AREI-RGIE Art.104-SA

Flame propagation

IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, SEV TP 20B/3C 3.4.1.1, AREI-RGIE Art.104-F1

Flame spread

IEC 60332-3-24 Cat. C, EN 60332-3-24 Cat. C, VDE 0482-332-3-24 Cat. C, SEV TP 20B/3C 3.4.1.3, AREI-RGIE Art.104-F2

Smoke density

IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, SEV TP 20B/3C 3.4.3, AREI-RGIE Art.104-SD

Circuit Integrity (FE180)

IEC 60331-11/-21 (180 minutes), VDE 0472 part 814 (FE180), IEC 60331-1, IEC 60331-2 (120 minutes ), EN 50200, VDE 0482-200 (PH120) and EN 50362, VDE 0482-362 (120 minutes), BS 6387 C/W/Z, AREI-RGIE Art.104-FR1

Documentation

ENDENLFRCNESIT
Product Datasheet

Versions

Article No.ProductNumber of CoresDiameter [mm²]Sheath Ø [mm]Weight [kg/km]Cu rate [kg/km]Fire load [kWh/m]ConstructionConductor
191118FE180 E30 2 x 1.521.57.8102290.22LNsolid
191119FE180 E30 2 x 2.522.59143480.28LNsolid
187180FE180 E30 3 x 1.531.58.3121430.25LNPEsolid
187184FE180 E30 3 x 2.532.59.5171720.31LNPEsolid
187187FE180 E30 3 x 434112431150.41LNPEsolid
187189FE180 E30 3 x 63612.53331730.51LNPEsolid
187182FE180 E30 4 x 1.541.59.1148580.293LPEsolid
190502FE180 E30 4 x 2.542.510.5211960.383LPEsolid
192352FE180 E30 4 x 44412.23041540.493LPEsolid
192353FE180 E30 4 x 64613.84152300.613LPEsolid
187183FE180 E30 5 x 1.551.59.9178720.353LNPEsolid
187186FE180 E30 5 x 2.552.511.62601200.473LNPEsolid
187188FE180 E30 5 x 45413.43711920.613LNPEsolid
187190FE180 E30 5 x 65615.25102880.763LNPEsolid
186267FE180 E30 7 x 1.571.510.8205100.80.416LPEsolid
186268FE180 E30 7 x 2.572.512.53211680.536LPEsolid
187201FE180 E30 7 x 67616.76524030.896LPEsolid
187108FE180 E30 8 x 1.581.511.92591150.487LPEsolid
188345FE180 E30 10 x 1.5101.513.83211440.699LPEsolid
186269FE180 E30 12 x 1.5121.514.2363172.80.6611LPEsolid
192479FE180 E30 12 x 2.5122.516.75422880.8811LPEsolid
187109FE180 E30 21 x 1.5211.517.75853030.9920LPEsolid
190412FE180 E30 27 x 1.5271.520.47553891.3026LPEsolid
Additional dimensions available on request.

Related products