(N)HXH CL FE180 E30-E60

Safety cable, 0.6/1kV armoured with rodent protection, Keram

halogen-free, with improved fire characteristics,
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E30-E60* in accordance with DIN 4102-12 

1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Inner sheath: Polyolefin, flame retardant, low smoke, zero halogen
6 Armouring: galvanised steel tape
7 Sheath: FRNC/LSZH

Description

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. These cables correspond to the demands of Circuit Integrity E30-E60* in accordance with DIN 4102-12. Circuit Integrity is guaranteed at an operating voltage up to 400V.
Permitted operating temperature at conductor of +90˚C.

ConductorBare copper, solid or stranded, IEC 60228, EN 60228, (VDE 0295)
InsulationDouble insulation, cross-linked, high-performance Keram special compound, VDE 0266 “HXI1”
FillerFlame retardant, halogen-free, thermoplastic compound
Inner sheathFlame retardant Polyolefin compound,CENELEC HD 604 S1 and VDE 0276-604 “HM4”
Armouring (rodent protection)Single-core cable with copper tape (CLCU) and multicore cable with galvanised steel tape (CL)
Outer sheathFlame retardant Polyolefin compound, CENELEC HD 604 S1 and VDE 0276-604 “HM4”
Core coloursCENELEC HD 308 S2 and VDE 0293
Sheath colourOrange
Nominal voltage0.6/1kV
Test voltage4000V, 50Hz
Minimum bending radiusduring and permanent installation

15 x D (single core cable)
12 x D (multicore cable)
(D = outer diameter)

Operating temperaturepermanent installation-45°C to +90°C
 during installation-5°C to +50°C
System Circuit Integrity is dependent on installation method.

Zero halogen, no corrosive gases

IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA

Flame propagation

IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1

Flame spread

IEC 60332-3-22/-24 Cat. A/C, EN 60332-3-22/-24 Cat. A/C, VDE 0482-332-3-22/-24 Cat. A/C, AREI-RGIE Art.104-F2

Circuit Integrity (FE180)

IEC 60331-11/-21 (180 minutes), VDE 0472 part 814 (FE180), IEC 60331-1, IEC 60331-2 (120 minutes ), EN 50200, VDE 0482-200 (PH120) and EN 50362, VDE 0482-362 (120 minutes), BS 6387 C/W/Z, AREI-RGIE Art.104-FR1

System circuit integrity

DIN 4102 part 12, AREI-RGIE Art.104-FR2

Documentation

ENDENLFRCNESIT
Product Datasheet
MPA Certificate

Versions

Article No.ProductNumber of CoresDiameter [mm²]Sheath Ø [mm]Weight [kg/km]Cu rate [kg/km]Fire load [kWh/m]ConstructionConductor
192350(N)HXH-O CL FE180 E30-E60 2 x 1.521.514.9334.3290.94LNsolid
187562(N)HXH-O CL FE180 E30-E60 2 x 2.522.516383.4481.02LNsolid
191612(N)HXH-O CL FE180 E30-E60 2 x 42417450.4771.13LNsolid
187563(N)HXH-O CL FE180 E30-E60 2 x 62618530.71151.25LNsolid
191107(N)HXH-J CL FE180 E30-E60 3 x 1.531.516363.4431.00LNPEsolid
186940(N)HXH-J CL FE180 E30-E60 3 x 2.532.516.3425.4721.10LNPEsolid
192351(N)HXH-J CL FE180 E30-E60 3 x 43418508.81151.22LNPEsolid
188326(N)HXH-J CL FE180 E30-E60 3 x 636196071731.35LNPEsolid
191597(N)HXH-J CL FE180 E30-E60 3 x 1031021785.12881.54LNPEsolid
188327(N)HXH-J CL FE180 E30-E60 3 x 16316241074.14611.93LNPEstranded
190590(N)HXH-J CL FE180 E30-E60 4 x 2.542.518484.2961.223LPEsolid
191102(N)HXH-J CL FE180 E30-E60 4 x 44419584.81541.363LPEsolid
192593(N)HXH-J CL FE180 E30-E60 4 x 64620709.42301.513LPEsolid
192594(N)HXH-J CL FE180 E30-E60 4 x 1041022939.63841.763LPEsolid
186980(N)HXH-J CL FE180 E30-E60 4 x 16416251292.56142.203LPEstranded
186981(N)HXH-J CL FE180 E30-E60 4 x 25425291813.69602.783LPEstranded
186982(N)HXH-J CL FE180 E30-E60 4 x 3543532229613443.163LPEstranded
190589(N)HXH-J CL FE180 E30-E60 4 x 50450363029.319204.022LNPEstranded
192428(N)HXH-J CL FE180 E30-E60 4 x 70470404014.926885.053LPEstranded
192429(N)HXH-J CL FE180 E30-E60 4 x 95495465343.536486.523LPEstranded
192430(N)HXH-J CL FE180 E30-E60 4 x 1204120496433.246087.263LPEstranded
192347(N)HXH-J CL FE180 E30-E60 5 x 1.551.518463.8721.253LNPEsolid
188117(N)HXH-J CL FE180 E30-E60 5 x 2.552.519555.51201.383LNPEsolid
188118(N)HXH-J CL FE180 E30-E60 5 x 45420675.21921.543LNPEsolid
186941(N)HXH-J CL FE180 E30-E60 5 x 65621825.52881.723LNPEsolid
186942(N)HXH-J CL FE180 E30-E60 5 x 10510241095.24801.983LNPEsolid
187154(N)HXH-J CL FE180 E30-E60 5 x 16516271452.17682.533LNPEstranded
190525(N)HXH-J CL FE180 E30-E60 5 x 16516261531.17682.533LNPEstranded
186984(N)HXH-J CL FE180 E30-E60 5 x 25525312167.612003.233LNPEstranded
187132(N)HXH-J CL FE180 E30-E60 5 x 35535352701.816803.853LNPEstranded
190529(N)HXH-J CL FE180 E30-E60 5 x 35535352801.416803.853LNPEstranded
187131(N)HXH-J CL FE180 E30-E60 5 x 5055039361324004.833LNPEstranded
191565(N)HXH-J CL FE180 E30-E60 5 x 50550393678.224004.833LNPEstranded
194049(N)HXH-J CL FE180 E30-E60 5 x 70570454998.933606.053LNPEstranded
188094(N)HXH-J CL FE180 E30-E60 6 x 46420692.62301.745LPEsolid
185232(N)HXH-J CL FE180 E30-E60 7 x 1.571.519530.81011.386LPEsolid
185245(N)HXH-J CL FE180 E30-E60 7 x 47421796.82691.716LPEsolid
185247(N)HXH-J CL FE180 E30-E60 7 x 67623984.74031.96LPEsolid
185248(N)HXH-J CL FE180 E30-E60 7 x 10710251339.86722.26LPEsolid
188095(N)HXH-J CL FE180 E30-E60 8 x 48423834.53071.917LPEsolid
185239(N)HXH-J CL FE180 E30-E60 12 x 2.5122.523945.22882.13LPEsolid
185233(N)HXH-J CL FE180 E30-E60 16 x 1.5161.524922.92302.2415LPEsolid
192725(N)HXH-J CL FE180 E30-E60 16 x 2.5162.52611543842.5215LPEsolid
185235(N)HXH-J CL FE180 E30-E60 30 x 1.5301.5301401.34323.2529LPEsolid
185241(N)HXH-J CL FE180 E30-E60 30 x 2.5302.5331838.87203.8129LPEsolid
Additional dimensions available on request.