J-H(St)H...Bd fire alarm

Fire alarm cable, max. 300V

halogen-free, with improved fire characteristics,
VDE 0815 

1 Conductor: solid
2 Insulatio: halogen-free polymer compound
3 Separator: plastic tape
4 Drain wire: tinned copper
5 Shielding: Al-laminated plastic foil
6 Sheath: FRNC/LSZH

Description

Installation cable with electrostatic shield for areas vulnerable to fire and with high concentration of people and property value. For ICT systems for lossless data and signal transmission. Suitable for laying in dry and humid rooms, on-wall and in-wall, also for outdoor use.
No underground laying. Not to be used for high-voltage transmission.
Permitted operating temperature at conductor of +70°C.

ConductorBare copper, solid, 0.6 or 0.8 mm diameter
InsulationHalogen-free polymer compound, EN 50290-2-26
Core idendificationDIN VDE 0815 (different colours)
StrandingCores twisted to star-quads and quads to units
ShieldingAl-laminated plastic foil with drain wire, copper tinned
Outer sheathHalogen-free polymer compound, EN 50290-2-27
Sheath colourRed
Rated voltagemax. 300V
Test voltage800V 50Hz
Conductor resistance Loop

0,6mm max. 130 Ω / km;

 

0,8mm max. 73,2 Ω / km

Insulation resistance

min. 100 MΩ x km

Capacitymax. 120 nF/km
Minimum bending radiuspermanent installation2.5 x D
 during installation7.5 x D (D = outer diameter)
Operating temperaturepermanent installation-30 °C bis +70 °C
 during installation- 5 °C bis +50 °C
Additional dimensions available on request.

Zero halogen, no corrosive gases

IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA

Flame propagation

IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1

Flame spread

IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Art.104-F2

Documentation

ENDENLFRCNESIT
Product Datasheet
Tender text

Versions

Article No.ProductNumber of PairsNumber of CoresDiameter [mm]Sheath colourSheath Ø [mm]Weight [kg/km]Cu rate [kg/km]Fire load [kWh/m]PU
157892J-H(St)H...Bd fire alarm 2x2x0.8 mm20.8 mmred6.559.325 kg\km0.16 Kwh/mby the metre
157893J-H(St)H...Bd fire alarm 4x2x0.8 mm420.8red8.5110450.29by the metre
157894J-H(St)H...Bd fire alarm 6x2x0.8 mm620.8red10.5130650.35by the metre
157895J-H(St)H...Bd fire alarm 10x2x0.8 mm1020.8red132201060.55by the metre
1172017J-H(St)H...Bd fire alarm 20x2x0.8 mm2020.8red15.55102061.21by the metre
1172018J-H(St)H...Bd fire alarm 30x2x0.8 mm3020.8red16.36003071.36by the metre
1172019J-H(St)H...Bd fire alarm 40x2x0.8 mm400.8 mmred16.5787407 kg\km1.67 Kwh/mby the metre
1172021J-H(St)H...Bd fire alarm 80x2x0.8 mm8020.8red31.514808093.18by the metre
1172022J-H(St)H...Bd fire alarm 100x2x0.8 mm10020.8red38.0181010104.07by the metre

Related products

NHXMH

Power cable, 300/500V

(N)HXM(St)H

Shielded power cable, 300/500V

N2XH

Safety cable, single-core, 0.6/1kV, Euroclass Cca