FE5-CL

Safety cable, 0.6/1kV, armoured with rodent protection

halogen-free, with improved fire characteristics,
with reference to SEV TP 20B/3C and CENELEC HD 604 S1 part 5. H 

1 Conductor: solid/stranded
2 Insulation: cross-linked PE, zero halogen
3 Inner sheath: Polyolefin, flame retardant, zero halogen
Armouring: galvanised steel tape
5 Sheath: FRNC/LSZH

Description

For permanent installation in dry, damp or wet areas, on or behind plasterwork or in walls or concrete. Also suitable for outdoor applications.
The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.

ConductorBare copper, solid or stranded, IEC 60228, EN 60228
InsulationCross-linked Polyethylene CENELEC HD 604 S1 part 5 sec. H
Inner sheathFlame retardant Polyolefin compound CENELEC HD 604 S1 part 5 sec. H
Armouring/rodent protectionSingle core cable with copper tape (CLCU) and
 Multicore cable with galvanised steel tape (CL)
Outer sheathFlame retardant Polyolefin compound CENELEC HD 604 S1 part 5 sec. H
Core coloursCENELEC HD 308 S2
Sheath colourBlack
Nominal voltage0.6/1kV
Test voltage3500V, 50Hz
Minimum bending radiusduring and permanent installation15* x D (single core cable)
  12* x D (multicore cable)
  (D = outer diameter)
Operating temperaturepermanent installation-45°C to +90°C
 during installation-5°C to +50°C
Additional dimensions available on request.

Zero halogen, no corrosive gases

IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA

Flame propagation

IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1

Flame spread

IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Art.104-F2

Smoke density

IEC 61034-1/-2, EN 61034-1/-2 , VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD

Documentation

ENDENLFRCNESIT
Product Datasheet

Versions

Article No.ProductNumber of CoresDiameter [mm²]Sheath Ø [mm]Weight [kg/km]Cu rate [kg/km]Fire load [MJ/m]ConstructionConductor
192730"FE5-CL-J 3 x 2.5"32.511190720.43LNPEsolid
191091"FE5-CL-J 3 x 4"34122401150.53LNPEsolid
191568"FE5-CL-J 3 x 10"310165152880.96LNPEsolid
191645"FE5-CL-J 3 x 6"36143501730.72LNPEsolid
191672"FE5-CL-J 4 x 1.5"41.510189580.383LPEsolid
192731"FE5-CL-J 5 x 4"54143751920.773LNPEsolid
190595"FE5-CL-J 5 x 6"56165102880.963LNPEsolid
191064"FE5-CL-J 5 x 2.5"52.5122701200.613LNPEsolid
188389"FE5-CL-J 5 x 10"510197604801.313LNPEsolid
190401"FE5-CL-J 5 x 16"5162412007682.173LNPEstranded
191063"FE5-CL-J 5 x 25"52528175012002.853LNPEstranded
191090"FE5-CL-J 5 x 35"53533240016803.943LNPEstranded
191036"FE5-CL-J 5 x 50"55037320024004.903LNPEstranded
191600"FE5-CL-J 5 x 95"59550605045608.643LNPEstranded
180930"FE5-CL-J 7 x 2.5"72.5133301680.715LNPEsolid
180929"FE5-CL-J 7 x 6"76176514031.156LPEsolid
184531"FE5-CL-J 7 x 10"710219806721.586LPEsolid
192240FE5-CL-J 12 x 2.5122.5175302881.2611LPEsolid