FE5-CL

Safety cable, 0.6/1kV, armoured with rodent protection, euroclass Dca

halogen-free, with improved fire characteristics,
with reference to SEV TP 20B/3C and CENELEC HD 604 S1 part 5. H

1 Conductor: solid/stranded
2 Insulation: cross-linked PE, zero halogen
3 Inner sheath: Polyolefin, flame retardant, zero halogen
Armouring: galvanised steel tape
5 Sheath: FRNC/LSZH

Description

For permanent installation in dry, damp or wet areas, on or behind plasterwork or in walls or concrete. Also suitable for outdoor applications.
The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90°C.
ConductorBare copper, solid or stranded, IEC 60228, EN 60228
InsulationCross-linked Polyethylene CENELEC HD 604 S1 part 5 sec. H
Inner sheathFlame retardant Polyolefin compound CENELEC HD 604 S1 part 5 sec. H
Armouring/rodent protectionSingle core cable with copper tape (CLCU) and
 Multicore cable with galvanised steel tape (CL)
Outer sheathFlame retardant Polyolefin compound CENELEC HD 604 S1 part 5 sec. H
Core coloursCENELEC HD 308 S2
Sheath colourBlack
Nominal voltage0.6/1kV
Test voltage3500V, 50Hz
Minimum bending radiusduring and permanent installation15* x D (single core cable)
  12* x D (multicore cable)
  (D = outer diameter)
Operating temperaturepermanent installation-45°C to +90°C
 during installation-5°C to +50°C
Additional dimensions available on request.

Reaction to fire (Euroclass)

EN 13501-6: Dca

Zero halogen, no corrosive gases

IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA

Flame propagation

IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1

Flame spread

IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Art.104-F2

Smoke density

IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD

Documentation

ENDENLFRCNESIT
Product Datasheet

Versions

Article No.DoPProductReaction to fire (Euroclass)Number of CoresCross section [mm²]Sheath Ø [mm]Weight [kg/km]Cu rate [kg/km]Fire load [kWh/m]ConstructionConductorPU
19628600DZFE5-CL 1 x 35Dca-s2,d1,a1135144883780.74Lstrandedby the metre
19621600DZFE5-CL-J 1 x 300Dca-s2,d1,a1130033335429763.61Lstrandedby the metre
19627500DZFE5-CL-J 2 x 1.5Dca-s2,d1,a121.58112290.28LNsolidby the metre
19586400DZFE5-CL-J 2 x 2.5Dca-s2,d1,a122.510153490.37LNsolidby the metre
19273000DZFE5-CL-J 3 x 2.5Dca-s2,d1,a132.510170720.41LNPEsolidby the metre
19109100DZFE5-CL-J 3 x 4Dca-s2,d1,a134112381150.48LNPEsolidby the metre
19156800DZFE5-CL-J 3 x 10Dca-s2,d1,a1310165052880.91LNPEsolidby the metre
19167200DZFE5-CL-J 4 x 1.5Dca-s2,d1,a141.59153580.363LPEsolidby the metre
19164500DZFE5-CL-J 3 x 6Dca-s2,d1,a136133331730.65LNPEsolidby the metre
19626100DZFE5-CL-J 4 x 2.5Dca-s2,d1,a142.511217960.483LPEsolidby the metre
19626400DZFE5-CL-J 5 x 1.5Dca-s2,d1,a151.510176720.453LNPEsolidby the metre
19106400DZFE5-CL-J 5 x 2.5Dca-s2,d1,a152.5122641200.593LNPEsolidby the metre
19273100DZFE5-CL-J 5 x 4Dca-s2,d1,a154143641920.733LNPEsolidby the metre
19059500DZFE5-CL-J 5 x 6Dca-s2,d1,a156164972880.923LNPEsolidby the metre
18838900DZFE5-CL-J 5 x 10Dca-s2,d1,a1510187434801.563LNPEsolidby the metre
19040100DZFE5-CL-J 5 x 16Dca-s2,d1,a15162411207682.033LNPEstrandedby the metre
19106300DZFE5-CL-J 5 x 25Dca-s2,d1,a152528171012002.763LNPEstrandedby the metre
19109000DZFE5-CL-J 5 x 35Dca-s2,d1,a153531.8227716803.443LNPEstrandedby the metre
19103600DZFE5-CL-J 5 x 50Dca-s2,d1,a155036314424004.743LNPEstrandedby the metre
19160000DZFE5-CL-J 5 x 95Dca-s2,d1,a159549585445608.163LNPEstrandedby the metre
18092900DZFE5-CL-J 7 x 6Dca-s2,d1,a176176334031.16LPEsolidby the metre
18453100DZFE5-CL-J 7 x 10Dca-s2,d1,a1710209646721.486LPEsolidby the metre