(N)HXCH FE180 E90

Safety cable, 0.6/1kV, Keram

halogen-free, with improved fire characteristics,
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E90 in accordance with DIN 4102-12 

1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Concentric conductor: bare copper wire
6 Reinforcing helix: bare copper tape
7 Separator: plastic tape
8 Sheath: FRNC/LSZH

Description

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. These cables correspond to the demands of System Circuit Integrity E90* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 400V.
Permitted operating temperature at conductor of +90˚C.
Operating temperature at conductor of +90˚C.

 

ConductorBare copper, solid or stranded, IEC 60228, EN 60228 (VDE 0295)
InsulationDouble insulation, cross-linked, high-performance Keram special compound, VDE 0266 “HXI1”
FillerHalogen-free compound or plastic tape
Concentric conductorBare copper wires with reinforced helix
SeparatorPlastic tape
Outer sheathPolyolefin compound, CENELEC HD 604 S1, VDE 0276-604 “HM4”
Core coloursCENELEC HD 308 S2 and VDE 0293
Sheath colourOrange
Nominal voltage0.6/1kV
Test voltage4000V, 50Hz
Minimum bending radiusduring and permanent installation

12 x D (multicore cable)
(D = outer diameter)

Operating temperaturepermanent installation-45°C to +90°C
 during installation-5°C to +50°C

* System Circuit Integrity is dependent on installation method.
 
Additional dimensions available on request.

Zero halogen, no corrosive gases

IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA

Flame propagation

IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1

Flame spread

IEC 60332-3-22/-24 Cat. A/C, EN 60332-3-22/-24 Cat. A/C, VDE 0482-332-3-22/-24 Cat. A/C, AREI-RGIE Art.104-F2

Smoke density

IEC 61034-1/-2, EN 61034-1/-2 , VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD

Circuit Integrity (FE180)

IEC 60331-11/-21 (180 minutes), VDE 0472 part 814 (FE180), IEC 60331-1, IEC 60331-2 (120 minutes ), EN 50200, VDE 0482-200 (PH120) and EN 50362, VDE 0482-362 (120 minutes), BS 6387 C/W/Z, AREI-RGIE Art.104-FR1

System circuit integrity

DIN 4102 part 12, VdS 3423 (single core cable ≥16mm2), AREI-RGIE Art.104-FR2

Documentation

ENDENLFRCNES
Product Datasheet
Tender text

Versions

Article NumberProductDimensions n x [mm2]ConductorSheath Ø [mm]Weight [kg/km]Cu rate
[kg/km]
Fire load [kWh/m]
186071(N)HXCH FE180 E90 3 x 1.5/1.5solid13.2248660.65
186195(N)HXCH FE180 E90 3 x 2.5/2.5solid14.13081040.72
186197(N)HXCH FE180 E90 3 x 4/4solid15.74041610.84
187278(N)HXCH FE180 E90 3 x 6/6solid16.85042400.94
187279(N)HXCH FE180 E90 3 x 10/10solid18.67274081.15
187406(N)HXCH FE180 E90 3 x 25/16stranded25.814969021.95
187251(N)HXCH FE180 E90 3 x 16/16stranded24.411666431.64
172417(N)HXCH FE180 E90 3 x 35/16stranded28.2182011902.25
187408(N)HXCH FE180 E90 3 x 50/25stranded32.5249317232.90
187409(N)HXCH FE180 E90 3 x 70/35stranded36.1335024103.42
187410(N)HXCH FE180 E90 3 x 95/50stranded42.0457032964.50
187411(N)HXCH FE180 E90 3 x 120/70stranded45.4562042365.02
187412(N)HXCH FE180 E90 3 x 150/70stranded50.7685051006.00
187413(N)HXCH FE180 E90 3 x 185/95stranded55.0835063837.10
187414(N)HXCH FE180 E90 3 x 240/120stranded62.11110082429.08
186198(N)HXCH FE180 E90 4 x 4/4solid16.84732000.96
186072(N)HXCH FE180 E90 4 x 1.5/1.5solid14.1286810.73
186199(N)HXCH FE180 E90 4 x 6/6solid18.16212971.13
186196(N)HXCH FE180 E90 4 x 2.5/2.5solid15.13581280.82
186200(N)HXCH FE180 E90 4 x 10/10solid20.18685041.33
186131(N)HXCH FE180 E90 4 x 16/16stranded25.314007961.81
186132(N)HXCH FE180 E90 4 x 25/16stranded28.9189511422.28
186133(N)HXCH FE180 E90 4 x 35/16stranded31.6237615262.60
186134(N)HXCH FE180 E90 4 x 50/25stranded36.7324922033.49
186135(N)HXCH FE180 E90 4 x 70/35stranded41.3442630824.25
186136(N)HXCH FE180 E90 4 x 95/50stranded46.4580942085.53
186137(N)HXCH FE180 E90 4 x 120/70stranded50.1713453886.25
186138(N)HXCH FE180 E90 4 x 150/70stranded55.3870365407.58
186139(N)HXCH FE180 E90 4 x 185/95stranded60.81082781599.18
172461(N)HXCH FE180 E90 12 x 2.5/4solid22.67983341.63
186140(N)HXCH FE180 E90 4 x 240/120stranded69.2141391054611.60
187402(N)HXCH FE180 E90 24 x 1.5/6solid27.49014132.32
186073(N)HXCH FE180 E90 7 x 1.5/2.5solid16.13931330.94
187403(N)HXCH FE180 E90 24 x 2.5/10solid30.612056962.69
191096(N)HXCH FE180 E90 7 x 2.5/2.5solid17.34912001.05
187404(N)HXCH FE180 E90 30 x 1.5/6solid29.112524992.67
187415(N)HXCH FE180 E90 12 x 1.5/2.5solid20.25952051.38
187405(N)HXCH FE180 E90 30 x 2.5/10solid32.216928403.11

Similar Products

(N)HXH FE180 E30-E60

Safety cable, 0.6/1kV, Keram

(N)HXCH FE180 E30-E60

Safety cable, 0.6/1kV, Keram

(N)HXH CL FE180 E30-E60

Safety cable, 0.6/1kV armoured with rodent protection, Keram