EN-60KDS

High-end Network insulator

Surge protection and galvanic isolation
in one compact Keystone module

 

Description

Compact 1-gigabit network isolator in Keystone construction suitable for device installation or permanent installation.
Can be used in any Keystone-compatible wall outlet panel.
When retrofitting existing installations its rear connecting cable acts as a simple extension.
Meets the performance requirements of TIA 568 Cat.5e and ISO 11801 Class D in the Permanent Link and is thus designed for transmissions of up to 1 gigabit per second.

In medical technology, recording studios, measuring and monitoring technology and in the potentialfree connection of remote computer systems.
Galvanic isolation of any device connected to a copper-based Ethernet network (wires and screen).
Suppresses potential equalisation currents and protects medical and non-medical equipment and systems from the consequences of dangerous network voltage surges which can be caused by switching operations, moisture, electrostatic discharge, differences in potential or lightning strike.
Attenuates low-frequency signal components so well that it effectively prevents ripple pickup in connected devices.

Electric strength:6000 VAC at 50 Hz (1 min.), 8500 VDC
Max. applied voltage (permanent):400 VAC at 50/60 Hz
Insertion Loss:< 1dB (1 MHz < f < 100 MHz)
Supported network protocols:IEEE802.3 10BaseT (Cl.14), 100BaseTx (Cl.25), 1000BaseT (Cl.40)
Labellings:CE, UL (E249126), RoHS compliant, lead-free
Operating conditions:Temperature: 10° bis 45° C / Air humidity: 10% up to 90%
 (non-condensing) / Barometric pressure: 860 hPa up to 1060 hPa
Length of connecting cable:20 cm = standard on stock, other lengths on request
(from 3 cm up to 10 m)
Dimensions
(housing w/o cable):
H x W x L = 23.5 x 17.3 x 39.9 mm

Datwyler is a distribution partner of EMO Systems GmbH

Standards

IEC 60601- 1:1988 A1:1991 and A2: 1995 (2nd Edition); IEC 60601-1-1:2000;
IEC 60601- 1: 2005 (3rd Edition); IEC 60601-1-2:2007; UL 60601;
IEC 61000-4-2 (ESD; 15kV Air / 8kV Contact); IEC 61000-4-4 (EFT; 40A, 5/50ns)
and IEC 61000-4-5 (Lightning; 12A 8/20 μs)

Documentation

ENDENLFRCNES
Product Datasheet

Versions

Article NumberProductDescriptionPU
417906 + lengh of cableEN-60KDSHigh-end network isolator EN-60KDS, length = ? cm1 pc.